SIS-AXS controller is an integrated multifunction high speed micro controller based System. It s having a provision of single phase/three phase mains and DG with Automatic /manual modes of operations. This controller includes protection for mains and DG (as per standards). This controller in having battery and room temperature monitoring facility.
System Controller system is designed for telecom sites it can used Like (PIU/IPMS/AMF). SISPL SIS-AXS controller unit has inbuilt Feature remote management, Energy Management and fault detection, power scalability, Etc. that enhance the fuel and battery efficiency in the existing sites. This controller follows a rational approach towards power management through
The highlighting feature of SIS-AXS controller is that it reduces the operational costs through a well-researched fuel management system The fault management and functionality units of this system is adaptable for Air-conditioners, Batteries, Fire alarms, Diesel Gen sets, Security, AC Power, DC power, lightening and surge protection, etc.
Description | Standard Specification |
---|---|
Capacity | Range of 5 to 50 KVA |
Multi Phase Logic | SIS-AXS controller will work on 1Phase, 2phase or 3Phase. Input voltage range on single phase – 145V–300V |
Mechanical | CNC Fabricated box, using CRC Sheet duly powder coated, 1.6 mm thick CRC sheet. Split type modular design. |
Safety | The equipment will ensure IEC 60950 safety standards |
MTBF | All material & workmanship will be of professional quality to ensure MTBF requirement. The MTBF of the AMF controller is more than 70000 hrs. |
Compliance | CE, Tested for safety, EMI/RFI compliance |
Micro Controller | High-Speed micro controller True RMS for all voltage & current All the inputs to the measurement board will be duly protected against surge as per IEEE-62.41 The measurement circuit will be rated at least twice of the maximum input range, each independent for AMF & module |
Time | Real time & date-programmable |
Event Logs | Last 2000 events |
RS 232t for SISPL use only | For PC interface to adjust the critical data and unload the alarms, This Port will be used for configuration of PFCs. |
Energy | Will be able to measure the DG energy (Cumulative KWH & Hrs) Will be able to measure the EB energy (Cumulative KWH & Hrs) Will be able to measure the Battery energy (Cumulative KWH & Hrs) |
Data Transfer | SIS-AXS controller will be equipped with suitable GPRS modem / GPRS DTU and able to process the data. |
DG on load | After DG starts and supply is healthy |
Blackout delay | 5 Seconds between mains and DG contactor changeover. |
DG cooling time | 15 minutes |
DG start attempts | Three attempts with delay between attempts ( 40 -40 -40 sec )(settable) |
DG Lock time | After three very short mains restoration 10-10-20 minutes, DG will run for 1hrs (settable) continuously. |
Stop Command duration | Settable from 10 to 50 seconds |
Battery charger & DG controller unit | Automatic DG battery, SMPS charger with boost/trickle charging & with constant cur¬rent charging facility (12V) Provision of Auto manual mode selection |
Auto Phase selector | The AMF Controller will be inbuilt with auto phase selector which will select any two phase or single phase out of 3 Phase. There will be a electrical and mechanical interlock between each contactor to avoid short circuit in case of electronic failure |
Auto Phase selector | The AMF Controller will be inbuilt with auto phase selector which will select any two phase or single phase out of 3 Phase. There will be a electrical and mechanical interlock between each contactor to avoid short cir¬cuit in case of electronic failure |
Set point-for high temperature alarm | Factory set (“ON” at 40°C and “OFF” at ON - 3°C) |
DG set measurements | Mains/DG status, DG accumulated hours, DG voltage, DG Energy Measurement (DG KWH) |
Mains measurements | Input Voltage, Output voltages for line conditioning module, Mains Energy Measurement (EB KWH) |
Battery measurements | Battery running hrs & KWH (Accumulated) |
LED Indications: | Mains ON, DG ON, Smoke/ Fire Alarm, DG Common Fault, Fuel Low, System battery low, High Shelter temperature |
List of potential free dry contacts | Alarms will be extended to NOC / TOC through changeover contact (both ‘NO’, ‘NC’). Mains fail, Shelter Door open/ Intruder, Low fuel level, Common fault -- LLOP/Alt fault/HCT/HWT/V belt/Dg fail to start/DG fail to stop, Smoke/Fire, Load on DG, DG Fail to stop, DG Fail to start, DG over load, Shelter high temperature, Site on battery, BTS Battery Low. |
Standard setting | Setting in the AMF Controller can change manually & Laptop. |
Site Calibration | All measured parameter can you calibrate through S/W on field |
Dual DG Logic | Will be provided the Dual dg logic on sequential basis. |
The configuration for controller module is as follows:-
S.NO | Parameter Name | Max Value | Min Value | Default Value |
---|---|---|---|---|
1. | MAINS HIGH CUTOFF | 500 | 240 | 300 |
2. | MAINS LOW CUTOFF | 350 | 70 | 90 |
3. | MAINS HIGH CUTIN | 500 | 220 | 290 |
4. | MAINS LOW CUTIN | 360 | 70 | 130 |
5. | DG HIGH CUTOFF | 280 | 240 | 260 |
6. | DG LOW CUTOFF | 210 | 140 | 170 |
7. | DG RPM HIGH | 3000 | 1550 | 1650 |
8. | DG RPM LOW | 1500 | 1000 | 1350 |
9. | ROOM TMP.HIGH ALARM | 60 | 15 | 40 |
10. | DG CRANK TEMP HIGH | 60 | 15 | 35 |
11. | DG OVERLOAD | 150 | 1 | 35 |
12. | EB OVERLOAD | 150 | 1 | 35 |
13. | BTS BATTERY LOW | 60.0 | 20.0 | 47.0 |
14. | DG AUTO RUN TIME | 18 | 1 | 6 |
15. | CRANK ACTIVE TIME | 10 | 1 | 3 |
16. | CRANK RETRIES | 5 | 0 | 2 |
17. | STOP HOLD TIME | 50 | 10 | 30 |
18. | STOP RETRIES | 5 | 0 | 2 |
19. | DG WARM UP TIME | 90 | 10 | 10 |
20. | MAINS RESTORE TIME | 300 | 20 | 30 |
20. | DG COOL DOWN TIME | 900 | 30 | 60 |
21. | DG LOCK TIME | 150 | 10 | 10 |
22. | LLOP DELAY TIME | 50 | 5 | 5 |
23. | DG START INTERVAL | 240 | 30 | 40 |
24. | CT RATIO | 250 | 25 | 125 |
25. | LLOP ENABLE/DISABLE | DISABLE | ||
26. | EB FLUCTION TIME | 30 | 1 | 20 |
27. | EQUALIZE CHG NORMAL | DISABLE | ||
28. | EQUALIZE CHG MANUALLY | DISABLE | ||
29. | BATTERY CHARGE INTERVAL | 1440 | 1 | 168 |
30. | BATTERY CHARGE TIME | 48 | 1 | 12 |
31. | AVIATION ON TIME IN HOUR | 23 | 0 | 18 |
32. | AVIATION ON TIME IN MINUTE | 59 | 0 | 0 |
33. | AVIATION OFF TIME IN HOUR | 23 | 0 | 6 |
34. | AVIATION OFF TIME IN MINUTE | 59 | 0 | 0 |
35. | SVR HIGH CUTOFF | 300 | 240 | 260 |
36. | SVR LOW CUTOFF | 210 | 150 | 180 |
37. | PSEL ENABLE/DISABLE | ENABLE | ||
38. | PSEL HIGH CUT OFF | 300 | 240 | 300 |
39. | PSEL LOW CUT OFF | 180 | 70 | 90 |
40. | PSEL HIGH CUTIN | 290 | 250 | 280 |
41. | PSEL LOW CUTIN | 200 | 70 | 120 |
42. | PHASE UNBALANCE | 90 | 20 | 50 |
S. No | Parameter name | Actual value | Measured value |
---|---|---|---|
1. | Main R-PH Voltage | xxx | xxx |
2. | Main Y-PH Voltage | xxx | xxx |
3. | Main B-PH Voltage | xxx | xxx |
4. | LCU#1 Voltage | xxx | xxx |
5. | LCU#2 Voltage | xxx | xxx |
6. | LCU#3 Voltage | xxx | xxx |
7. | DG R-PH Voltage | xxx | xxx |
8. | DG Y-PH Voltage | xxx | xxx |
9. | DG B-PH Voltage | xxx | xxx |
10. | EB I/P current R-Phase | xxx | xxx |
11. | EB I/P current Y-Phase | xxx | xxx |
12. | EB I/P current B-Phase | xxx | xxx |
13. | O/P current R-Phase | xxx | xxx |
14. | O/P current Y-Phase | xxx | xxx |
15. | O/P current B-Phase | xxx | xxx |
16. | Room Temperature | xxx | xxx |
17. | Ambient Temperature | xxx | xxx |
18. | BTS Battery voltage | xxx | xxx |
19. | DG Battery voltage | xxx | xxx |
Actual values display what have you apply and measured value is measurement by controller.
The calibration parameters are as follows:-
There are five switches in Display Board
#SW1:
#SW2:
#SW3:
#SW4:
#SW5:
For any analog parameter calibration, you can go for calibration mode by configuration. In calibration mode you can go for that parameter which you want to calibrate. After you can set the value by increment and decrement key if actual value is equal to apply value press enter key and then press the escape key. And check that parameter is ok or not.
For any programmable parameter changing you can go in menu setting by configuration mode. In configuration mode you can go for that parameter which you want to change after this you can adjust by increment and decrement key and then press enter key. Then go for escape.
The operation of SIS-AXS controller in two ways on is AUTO mode and other is manual mode. In auto mode controller control the DG function automatically and check the DG alarm status but in manual mode no control the DG operation. In auto mode when mains or LCU voltage out of range or not available then check BTS battery voltage if BTS battery voltage is below of specified limit and room temperature is above limit, then check DG alarm status if no fault of DG after that check for LLOP if LLOP enable and connected properly and LED indication of LLOP should be off, if not then show in LCD display LLOP OPEN and not DG start. After checking the LLOP give the crank for DG start and wait for DG voltage if DG voltage is not coming within 30 seconds after given the crank, then give again crank for DG start and wait for DG voltage. If DG voltage is not coming after DG start the show DG fail to start and LED indication of fail to start should on. But if DG voltage is coming and within range then go for DG warm up otherwise generate the DG ALT fault. After DG warm upload is on and LCD display show DG OK. And check DG alarm like LLOP, Half FUEL, Low FUEL, HCT, overload, over speed. If any alarm generated, then give DG stop command. If DG is not stop after successful stop command, then show for DG fail to stop and LED indication of fail to start will on. If no alarm is generated and mains healthy that case DG will go for stop and after DG stop load will change on mains.
If DG is running and any DG fault is generated, or mains is restored then go for DG stop and after stop hold time DG is not stop then fail to stop alarm is generated. LED indication of fail to stop is continuing. Fail to stop and DG common fault relays will ON.
If DG crank is active and DG voltage is not coming within 30 seconds, then fail to start alarm is generated. LED indication of fail to start is continuing ON. Fail to start and DG common fault relays will ON.
If DG is running and LLOP sensing input is close, then LLOP fault is generated. LED indication of LLOP is continuing. LLOP and DG common fault relays will ON.
If DG is running and Low fuel sensing input is close, then Low fuel alarm is generated. LED indication of low fuel is continuing. Fuel relay will ON.
If DG is running and half fuel sensing input is close, then half fuel alarm is generated. Fuel relay will ON.
If DG is running and HCT sensing input is close, then high engine temperature fault is generated. LED indication of HCT/HWT is continuing. HCT/HWT and DG common fault relays will ON.
If DG is running and output load of any phase is greater than specified limit, then over load fault is generated. LED indication of overload continuing ON. Overload and DG common fault relays will ON. Overload alarms check also for mains.
If DG is running and DG speed is out of range, then over speed alarm is generated. LED indication of over speed is continuing. Over speed and DG common fault relays will ON.
If DG is running and DG voltage is out of range, then DG alternate fault is generated. LED indication of alt fault is continuing on. DG common fault relay will ON.
If Mains or DG running and smoke fire sensing input is close, then smoke fire alarm is generated in this case mains and DG contractor is off. LED indication smoke fire alarm is continuing on and relay of smoke fire will ON.
If BTS battery voltage is below than specified limit, then BTS battery alarm is generated. LED indication of BTS battery low and Relay of BTS battery is continuing on.
If DG battery voltage is below than specified limit then DG battery alarm is generated. LED indication of DG battery low and Relay of DG battery is continuing on.
If room temperature is greater than specified limit then high room temperature alarm is generated. LED indication of high room temperature and Relay of high room temperature is continuing on.
When system is power on real time clock is running, when real time clock time is match is aviation on time then aviation lamp relay is on and if time is match of aviation off time then relay is off.
When these alarm is generated the controller is logged that alarm in date and time stamping format. Logging format given below. In this controller 1000 event logging is possible like first in first out (FIFO).
Site Management
1. Effective Resource allocation
2. Equipment performance history
3. Inventory Records
Failure Management
1. Early fault identification
2. Site up status and nature of faults
3. Remote Intervention
Equipment Evaluation
1. Site Battery condition
2. DG battery condition
3. Site temperature
Energy Management
1. DG Energy
2. EB Energy
3. Battery Energy
Billing (Optional)
1. Diesel Supplies
2. Grid consumption
Basic Information
Detailed Parameter Monitoring
Remote Operation
DC Energy Metering Customers wise
Fuel monitoring
Effective Resource allocation
Equipment performance history
Inventory Records
Early fault identification
Site up status and nature of faults
Remote Intervention
Site Battery condition
Site temperature
Site temperature
Solar Energy
EB Energy, Battery Energy
DG Energy (Optional)